Description
Application
These cables are used for internal wiring of panels and electrical equipment. These are used as connection wire in machines laid in protective tubes and flexible pipes and also for motors and transformers.
Technical Data
- Standard: UL 1015, 758, CSA C 22.2 No 210 & BS 6231
- Nominal Voltage: 600V UL – Type AWM 105°C 600V CSA – Type AWM 105°C 600V BS 6231 CK type 90°C 600V / 1000 V
- Test Voltage (Spark Test): AWG 18 to 16 : 6kV ≥ AWG 8: 7.5kV
- Temperature Range: Flexing -5°C to +105°C. Fixed installation -20°C to +105°C
- Bending Radius :
- Cable diameter ≤ 8 mm: 4 x outer diameter
- Approx diameter > 8 to 12 mm: 5 x outer diameter
- Approx diameter > 12 mm: 6 x outer diameter
Cable Construction
- Stranded copper conductor / according to BS EN 60228, cl. 5. PVC-core insulation according to UL – Standard 1581, Class 43 and CSA – C22.2 No. 210 ULVW – 1 and CSA FT – 1, heat and damp resistant
Properties
- Conditionally resistant to – Oils, Solvents, Acids, Dye.
- PVC self – extinguishing and flame retardant, test method to UL VW-1 and CSA FT 1 / FT 2
- Flame retardant to EN 60332 – 1- 2.
Cable Design Parameters
Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the insulation colour required: 01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green/yellow, 07 – white, 08 -Violet, 09 – brown, 10 – orange, 11 – pink, 12 – grey, 13 – light blue
| Part Number | AWG No. | No. of Cores & Nominal Cross Sectional (Sq. mm) | Approx. Cable Diameter (mm) | Approx. Copper Weight (kg/km) | Approx. Cable Weight (kg/km) |
|---|---|---|---|---|---|
| 060101010130 | 21 | 1 x 0.5 | 2.6 | 4.1 | 11.0 |
| 060101020230 | 19 | 1 x 0.75 | 2.8 | 6.1 | 13.5 |
| 060101030330 | 18 | 1 x 1 | 2.9 | 8.1 | 16.0 |
| 060101040430 | 16 | 1 x 1.5 | 3.2 | 11.7 | 21.0 |
| 060101050530 | 14 | 1 x 2.5 | 3.6 | 19.5 | 31.0 |
| 060101060630 | 12 | 1 x 4 | 4.1 | 31.5 | 45.0 |
| 060101070730 | 10 | 1 x 6 | 4.7 | 47.1 | 63.0 |
| 060101080830 | 8 | 1 x 10 | 6.3 | 81.6 | 111.0 |
| 060101090930 | 6 | 1 x 16 | 8.3 | 131.8 | 183.0 |
| 060101101030 | 4 | 1 x 25 | 9.6 | 204.8 | 267.0 |
| 060101111130 | 2 | 1 x 35 | 10.8 | 299.7 | 374.0 |
| 060101121230 | 1 | 1 x 50 | 13.2 | 416.8 | 531.0 |
| 060101131330 | 2/0 | 1 x 70 | 14.9 | 597.2 | 733.0 |
| 060101141430 | 3/0 | 1 x 95 | 16.4 | 774.0 | 928.0 |
| 060101151530 | 4/0 | 1 x 120 | 18.0 | 980.0 | 1156.0 |
| 060101161630 | 250 kcmil | 1 x 150 | 20.3 | 1208.1 | 1439.0 |
| 060101171730 | 350 kcmil | 1 x 185 | 22.4 | 1568.2 | 1834.0 |
| 060101181830 | 450 kcmil | 1 x 240 | 24.7 | 2018.2 | 2324.0 |
Note: For current ratings & voltage drop refer table no. 8-1.
CPR Compliance: Construction Product Regulation (CPR) is a regulation issued by the European Union to regulate fire resistance and dangerous substances in construction materials. The above link provides the Declaration of Performance (DOP) for CPR compliance of the product.