Fire Survival Cable BS 7846

Description

Application

The cable is designed to have a robust halogen free construction suitable for operation up to 1100V applications. It is ideal for wiring installations supplying critical loads that require supply integrity during fire conditions. These cables ensure continued operation of vital circuits even in the event of a fire outbreak.

Technical Data

  • Voltage Rating: 1100 Vac and 1500 Vdc
  • Operating Temperature Range: -5°C to +90°C (Fixed installation)
  • Minimum Bending Radius: 12 × overall cable diameter

Cable Construction

Conductor: Electrolytic annealed plain / tinned copper (Class 1/2) as per IS 8130.

Primary Insulation: Mica Tape Layer(s)

Secondary Insulation: Cross-linked PE (XLPE) / Cross-linked HFFR.

Core Colours:
1 Core – Red, Black, Yellow, Blue or Natural
2 Core – Red & Black
3 Core – Red, Yellow & Blue
4 Core – Red, Yellow, Blue & Black
5 Core – Red, Yellow, Blue, Black & Grey
6 Core and above – Number coded

Inner Sheath: Thermoplastic HFFR

Heat Barrier / Fire Resistant Layer: Mica Tape

Armour (optional): Galvanized Steel Wire / Strip Armour

Outer Sheath: Specially formulated HFFR compound providing low smoke and halogen-free performance.

Properties

  • Halogen Free, Low Smoke, Flame Retardant
  • Maintains circuit integrity under fire conditions
  • Compliant with IEC 60331 and IS 7098 (Part 1)
  • Excellent dielectric strength and thermal stability

Cable Technical Data

2 Core

Part Number Nominal Cross Sectional Area (Sq. mm) Insulation Thickness (mm) Nominal Armour Wire Diameter (mm) Approx. Diameter Under Armour (mm) Approx. Overall Diameter (mm) Approx. Cable Weight (kg/km) Max. DC Resistance @20°C (Ω/km) Max. AC Resistance @90°C (Ω/km) Reactance @50Hz (Ω/km) AC Impedance @90°C (Ω/km) Max. Armour Resistance @20°C (Ω/km)
100300201105 1.5* 0.6 0.9 8.5 13.0 415 12.1 15.428 0.104 15.428 10.7
100300201205 2.5* 0.7 0.9 10 14.5 495 7.41 9.448 0.101 9.448 8.8
100300200004 4* 0.7 0.9 11 15.5 575 4.61 5.878 0.099 5.878 7.9
100300200006 6* 1 0.9 12.5 17.0 658 3.08 3.927 0.094 3.928 7.0
100300200010 10* 1 0.9 14.0 19.0 828 1.83 2.333 0.093 2.335 6.0
100300200016 16 1 1.25 16.0 21.5 1005 1.15 1.466 0.088 1.469 3.8
100300200025 25 1 1.25 15.5 21.2 1105 0.727 0.927 0.082 0.93 3.7
100300200035 35 1 1.6 17.5 24.0 1555 0.524 0.668 0.077 0.673 2.5
100300200050 50 1 1.6 20.0 26.5 1855 0.387 0.494 0.076 0.5 2.3
100300200070 70 1.1 1.6 23.0 30.0 2455 0.268 0.342 0.075 0.349 2.0
100300200095 95 1.1 2.0 26.0 34.0 3345 0.193 0.247 0.074 0.258 1.4
100300200120 120 1.2 2.0 29.0 37.0 3898 0.153 0.196 0.072 0.209 1.3
100300200150 150 1.4 2.0 32.0 40.0 4645 0.124 0.16 0.073 0.176 1.2
100300200185 185 1.6 2.5 36.0 45.5 5945 0.0991 0.128 0.073 0.148 0.82
100300200240 240 1.7 2.5 40.0 50.0 7345 0.0754 0.099 0.072 0.122 0.73
100300200300 300 1.8 2.5 44.0 54.5 8695 0.0601 0.08 0.072 0.107 0.67
100300200400 400 2 2.5 49.5 60.0 10745 0.047 0.064 0.071 0.096 0.59


3 Core

Part Number Nominal Cross Sectional Area (Sq. mm) Insulation Thickness (mm) Nominal Armour Wire Diameter (mm) Approx. Diameter Under Armour (mm) Approx. Overall Diameter (mm) Approx. Cable Weight (kg/km) Max. DC Resistance @20°C (Ω/km) Max. AC Resistance @90°C (Ω/km) Reactance @50Hz (Ω/km) AC Impedance @90°C (Ω/km) Max. Armour Resistance @20°C (Ω/km)
100300301105 1.5* 0.6 0.9 9.0 13.5 423 12.1 15.428 0.104 15.428 10.2
100300301205 2.5* 0.7 0.9 10.5 15.0 544 7.41 9.448 0.101 9.448 8.2
100300300004 4* 0.7 0.9 11.5 16.5 644 4.61 5.878 0.099 5.878 7.5
100300300006 6* 0.7 0.9 13.0 17.5 738 3.08 3.927 0.094 3.925 6.6
100300300010 10* 0.7 1.25 15.0 20.5 1085 1.83 2.333 0.093 2.335 4.0
100300300016 16 0.7 1.25 17.0 22.5 1313 1.15 1.466 0.088 1.469 3.6
100300300025 25 0.9 1.6 20.0 26.5 1803 0.727 0.927 0.082 0.93 2.5
100300300035 35 0.9 1.6 22.0 29.0 2202 0.524 0.668 0.077 0.673 2.3
100300300050 50 1.0 1.6 22.5 29.5 2453 0.387 0.494 0.076 0.5 2.0
100300300070 70 1.1 1.6 26.0 33.0 3202 0.268 0.342 0.075 0.349 1.8
100300300095 95 1.1 2.0 30.0 38.0 4455 0.193 0.247 0.074 0.258 1.3
100300300120 120 1.2 2.0 33.0 41.5 5305 0.153 0.196 0.072 0.209 1.2
100300300150 150 1.4 2.5 37.0 46.5 6705 0.124 0.16 0.073 0.176 0.78
100300300185 185 1.6 2.5 41.0 51.0 8052 0.0991 0.128 0.073 0.148 0.71
100300300240 240 1.7 2.5 46.0 56.0 9953 0.0754 0.099 0.072 0.122 0.63
100300300300 300 1.8 2.5 51.0 61.0 12053 0.0601 0.08 0.072 0.107 0.58
100300300400 400 2.0 2.5 57.0 67.5 14803 0.047 0.064 0.071 0.096 0.52

4 Core

Part Number Nominal Cross Sectional Area (Sq. mm) Insulation Thickness (mm) Nominal Armour Wire Diameter (mm) Approx. Diameter Under Armour (mm) Approx. Overall Diameter (mm) Approx. Cable Weight (kg/km) Max. DC Resistance @20°C (Ω/km) Max. AC Resistance @90°C (Ω/km) Reactance @50Hz (Ω/km) AC Impedance @90°C (Ω/km) Max. Armour Resistance @20°C (Ω/km)
100300401105 1.5* 0.6 0.9 10 14.8 522 12.1 15.428 0.104 15.428 9.5
100300401205 2.5* 0.7 0.9 11.5 16.0 618 7.41 9.448 0.101 9.448 7.7
100300400004 4* 0.7 0.9 13 17.8 725 4.61 5.878 0.099 5.878 6.8
100300400006 6* 0.7 1.25 14.5 20.0 985 3.08 3.927 0.094 3.925 4.3
100300400010 10* 0.7 1.25 16.5 22.0 1255 1.83 2.333 0.093 2.335 3.7
100300400016 16 0.7 1.25 19 24.5 1635 1.15 1.466 0.088 1.469 3.2
100300400025 25 0.9 1.6 22 28.5 2145 0.727 0.927 0.082 0.930 2.3
100300400035 35 0.9 1.6 24.5 31.5 2645 0.524 0.668 0.077 0.673 2
100300400050 50 1.0 1.6 26 33.2 3103 0.387 0.494 0.076 0.500 1.8
100300400070 70 1.1 2.0 30.5 39.2 4405 0.268 0.342 0.075 0.349 1.2
100300400095 95 1.1 2.0 34.5 43.2 5653 0.193 0.247 0.074 0.258 1.1
100300400120 120 1.2 2.5 38.5 48.6 7252 0.153 0.196 0.072 0.209 0.76
100300400150 150 1.4 2.5 42.5 53.0 8553 0.124 0.16 0.073 0.176 0.68
100300400185 185 1.6 2.5 47.5 58.0 10203 0.0991 0.128 0.073 0.148 0.59
100300400240 240 1.7 2.5 53.0 64.0 12253 0.0754 0.099 0.072 0.122 0.54
100300400300 300 1.8 2.5 58.5 70.0 14453 0.0601 0.08 0.072 0.107 0.49
100300400400 400 2.0 2.5 65.0 77.5 17353 0.047 0.064 0.071 0.096 0.45

* Class 2 stranded circular (non compacted) conductor.

* For current ratings refer table no. 15-1 & voltage drop refer table no. 15-2.