PROcess FIeld BUS

Description

Application

PROcess FIeld BUS is a standard for fieldbus communication in automation technology. It links controllers or control systems with decentralized field devices (sensors and actuators) via a single bus cable on the field level. It also enables consistent data exchange with higher ranking communication systems.

PROcess FIeld BUS DP supports fieldbus solutions in factory and process automation as well as motion control and safety-related tasks using a single, standardized, application-independent protocol. Uniformity is ensured by “application profiles” referring to device families or special industry requirements.

PROcess FIeld BUS DP carries communication data between a controller and field devices (Factory Automation), while PROcess FIeld BUS PA is connected through couplers for typical process automation applications. PA segments can also interface directly with PROcess FIeld NET for MES/ERP integration.

Technical Data

  • Standard: Adapted to DIN 19245 & EN 50170
  • Operating Voltage: 250V (not for power installation)
  • Insulation Resistance: 5000 GΩ x cm
  • Temperature Range: Flexing 12 x cable ø, Fixed 6 x cable ø
  • Minimum Bending Radius: Flexing 12 x cable ø, Fixed installation 6 x cable ø
  • Test Voltage: 1500V
  • Flame Retardant: Complies with IEC 60332-1-2

Cable Design Parameters

  • Bare copper stranded 7 wire conductor.
Variant Size / Configuration Construction Application Sheath Colour Approx. Cable Dia. (mm)
Li2Y(St)CYv (TP) 22 AWG x 1PR (0.32 Sq. mm) ABC solid/Foam PE/PETP/AL Mylar/ATC Braid 65%/PVC Outer sheath Fixed installation, indoor usage Violet 8.0
02Y(St) C11Y DP 22 AWG x 1PR (0.32 Sq. mm) ABC solid/Foam PE/PETP/AL Mylar/ATC Braid 65%/PUR Outer sheath Fixed installation, Industrial Area Black 8.0
02Y(St)CY DP Armoured 22 AWG x 1PR (0.32 Sq. mm) ABC solid/Foam PE/PETP/AL Mylar/ATC Braid 65%/PVC Inner sheath/GI armour/PVC Outer sheath Direct Burial Black (Outer), Inner Violet 13.0
PROcess FIeld BUS PA Solid 18 AWG x 1PR (0.8 Sq. mm) ABC solid/Foam PE/PETP/AL Mylar/ATC Braid 65%/PVC Outer sheath Fixed installation, indoor usage Blue 9.2
02Y(St)CY PA Armoured 18 AWG x 1PR (0.8 Sq. mm) ABC solid/Foam PE/PETP/AL Mylar/ATC Braid 65%/PVC Inner sheath/GI armour/PVC Outer sheath Direct Burial Black (Outer), Inner Blue 14.0

Electrical Parameters

  • PROcess FIeld BUS DP:
  • Conductor Resistance: 110 Ω/km (Max)
  • Mutual Capacitance: 35 nF/km (Max)
  • Inductance: 0.65 mH/km (Nom.)
    Frequency Characteristic Impedance (Ω) Attenuation (dB/100m)
    9.6 kHz 270 ± 27 ≤ 0.25
    38.4 kHz 185 ± 18.5 ≤ 0.40
    4 MHz 150 ± 15 ≤ 2.2
    16 MHz 150 ± 15 ≤ 4.2

PROcess FIeld BUS PA

  • Conductor Resistance (Loop) at 20°C: 44 /km (Max.)
  • Mutual Capacitance: 55 nf/km (Max.)
  • Characteristic Impedance @ 31.25 kHz: 100 ± 15
  • Attenuation @ 39 Khz: ≤ 3 dB/km
  • Inductance: 0.65 mH/km (Nom.)

Baud Rate / Segment Length

Baud Rate (kbit/s) Segment Length (Meters) Segment Length (Feet)
9.6 1200 3940
19.2 1200 3940
45.45 1200 3940
93.75 1200 3940
187.5 1000 3280
500 400 1310
1500 200 656
3000 100 328
6000 100 328
12000 100 328

More Variants Available

  • PROcess FIeld BUS: DP and PA for flexible applications
  • PROcess FIeld BUS: DP and PA with steel braid
  • Halogen free variant with Low Smoke Zero Halogen (LSZH) outer sheath.

Notes

  • HART = Highway Addressable Remote Transducer
  • DP = Decentralized Peripherals
  • PA = Process Automation
  • More variants available: DP and PA for flexible applications, with steel braid, or halogen-free LSZH outer sheath
Cart (0 items)